Computer EIA RS-232 Cable, 24 AWG stranded (7×32) tinned copper conductors, semi-rigid PVC insulation, 1 twisted pair, overall Beldfoil® shield (100% coverage), 24 AWG stranded tinned copper drain wire, PVC jacket.
| Suitable Applications | RS-232 Applications; Computer Communications; Low Voltage Analog Signals (4-20ma, 0-10v, …); Low Voltage Digital Control (24v, …); Line Level Audio; Panel Wiring |
|---|
Conductor
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Pair(s) | 1 | 24 AWG | 7×32 | TC – Tinned Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Pair(s) | SR-PVC – Polyvinyl Chloride (Semi-Rigid) | 0.011 in (0.28 mm) | 0.044 in (1.1 mm) | Black & Red |
Outer Shield
| Shield Type | Material | Coverage | Drainwire Type |
|---|---|---|---|
| Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (7×32) TC |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter |
|---|---|---|
| PVC – Polyvinyl Chloride | 0.032 in (0.81 mm) | 0.156 in (3.96 mm) |
| Overall Cable Diameter (Nominal) | 0.156 in (3.96 mm) |
|---|
Electricals
| Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Velocity of Prop. | Max. Current |
|---|---|---|---|---|---|
| Pair(s) | 24 Ohm/1000ft | 40 pF/ft (130 pF/m) | 74 pF/ft (240 pF/m) | 60% | 2.2 Amps per Conductor at 25ºC |
Voltage
| UL Voltage Rating |
|---|
| 300 V (CMG), 300 V (UL AWM 2464) |
Temperature
| UL Temperature | Operating |
|---|---|
| 80°C | -30°C to +80°C |
Bend Radius
| Stationary Min. | Installation Min. |
|---|---|
| 1.6 in (41 mm) | 1.6 in (41 mm) |
| Max. Pull Tension | 17 lbs (7.7 kg) |
|---|---|
| Bulk Cable Weight | 12 lbs/1000ft |